Based in Enfield. Working across Adelaide and regional SA. 08 8151 1040

RCD and safety switch testing in Adelaide

RCD testing checks that your safety switches cut the power fast enough to prevent a fatal electric shock, and WHS regulation 165 requires workplaces to have their RCDs tested regularly by a competent person, with records kept. How often depends on your workplace and the type of RCD, and we quote per site.

Our technician working at the main switch of a commercial distribution board

What RCD testing is

A residual current device (RCD), or safety switch, watches the current flowing out and back through a circuit. If some of that current leaks to earth, for example through a person touching a faulty tool, the RCD cuts the power in a fraction of a second. Fast tripping is what stops a shock from being fatal.

RCDs are mechanical devices. Dust, moisture, age and lack of use can make them slow to trip or stop them working at all, and nothing on the outside shows it. Testing is the only way to know an RCD will work when it is needed.

RCD test requirements in South Australia

The rules are in the Work Health and Safety Regulations 2012 (SA).

Requirement What it means for you Regulation
Use RCDs in hostile environments Plug-in equipment exposed to damage, moved around or used with amusement devices must be protected by an RCD 164
Tripping current For socket outlets up to 20 A, the RCD must trip at no more than 30 mA 164
Regular testing RCDs must be tested regularly by a competent person to make sure they are working 165
Records Keep a record of each test (other than daily push-button tests) until the next test, or until the RCD is permanently removed 165
Faulty RCDs Take a faulty RCD out of service and replace it as soon as possible Code of practice: managing electrical risks in the workplace
Construction sites Follow AS/NZS 3012 for site electrical installations 163

Regulation 164 does not apply to supplies of 50 V AC or less, to direct current, or where power comes through an isolating transformer or an isolated-winding portable generator that gives equivalent protection.

AS/NZS 3760:2022 is the Australian Standard for in-service testing of electrical equipment, including RCDs. It is guidance rather than law in South Australia, but it sets the test methods and the intervals most workplaces use.

How often RCDs should be tested

The law says “regularly” and leaves the interval to your risk assessment. AS/NZS 3760:2022 sets intervals for two kinds of test, and those intervals depend on the environment and on whether the RCD is portable or fixed. SafeWork SA publishes them in this form:

Workplace Push-button test by user, portable Push-button test by user, fixed Trip-time test, portable Trip-time test, fixed
Factories, workshops, places of manufacture, assembly, maintenance or fabrication Daily, or before every use, whichever is longer 6 months 12 months 12 months
Equipment or cord flexed in normal use, or in a hostile environment 3 months 6 months 12 months 12 months
Equipment or cord not flexed in normal use, not open to abuse and not in a hostile environment 3 months 6 months 2 years 2 years
Residential type areas, such as hotels, motels, hostels and boarding houses 6 months 6 months 2 years 2 years
Commercial cleaning equipment Daily, or before every use, whichever is longer Not applicable 6 months Not applicable
Construction and demolition sites After connecting to a socket and before connecting equipment, and at least once every day in use 1 month 3 months 12 months

As a rule of thumb, the harsher the environment and the more often equipment is moved, the more often its RCD should be tested. Construction sites, workshops and outdoor work sit at the frequent end. Offices sit at the other.

For a fuller explanation, see our guide to how often RCDs should be tested.

Push-button tests and trip-time tests

The push-button test checks that the RCD’s mechanism works. Pressing the “T” or “Test” button creates a small imbalance and the switch should trip. It is quick, anyone can do it, and records of daily push-button tests are not required.

The trip-time test uses an RCD tester to apply a measured fault current and time how long the RCD takes to cut the power. This is the test that shows whether an RCD is fast enough. It is done by a competent person, and the result is recorded.

An RCD that passes the push-button test can still fail the trip-time test, so the two are not interchangeable.

Portable and fixed RCDs

  • Portable RCDs plug into a power point and protect whatever is plugged into them. They are common on construction sites and with outdoor equipment, and they are tested and tagged like other portable equipment.
  • Fixed RCDs sit in the switchboard and protect whole circuits. Testing them briefly cuts power to those circuits, so we plan the test with you. Replacing a fixed RCD is electrical work for a registered electrical worker.

Tell us whether your RCDs are portable, in the switchboard or both when you book, and we’ll confirm how the fixed ones will be tested.

Who needs RCD testing

Any workplace that relies on RCDs needs them tested, but some need it more often or face closer scrutiny:

  • Construction and demolition sites, where leads and tools are moved daily and exposed to weather and damage
  • Workshops, factories and warehouses, with heavy equipment, dust and vibration
  • Commercial kitchens and cleaning businesses, where water and electricity meet
  • Hire companies and event suppliers, whose equipment changes hands constantly
  • Schools, childcare, aged care and healthcare, where the people protected may not be able to react to a fault
  • Offices and shops, where switchboard RCDs protect every circuit in the tenancy

If you are not sure whether your workplace counts as a hostile environment, we can assess it on the first visit and suggest a test interval to put in your records.

What you get

Every RCD we test is listed in a written record with its location, type, test results, the date and the next test due. Portable RCDs are tagged. Any RCD that fails is reported straight away so it can be taken out of service. RCD testing is often booked with test and tag on the same visit, which saves a second call-out.

Standards and service frequency in SA

EquipmentHow oftenStandardSA source
RCDs on plug-in equipment in hostile environments Required where equipment is exposed to damaging conditions, moved around or used with amusement devices WHS Regulations 2012 (SA), regulation 164 (30 mA maximum tripping current, outlets up to 20 A) SafeWork SA
Testing of RCDs Regularly, by a competent person, with records kept until next test. SafeWork SA's table gives push-button and trip-time intervals by type of workplace WHS Regulations 2012 (SA), regulation 165, and AS/NZS 3760:2022 (guidance) SafeWork SA
Construction site electrical installations Throughout construction and demolition work WHS Regulations 2012 (SA), regulation 163, and AS/NZS 3012 SafeWork SA

Who this is for

Certificates and reporting

Every visit ends with a written report listing each item tested, its location and result, and anything that needs attention. Building owners use it as the maintenance record behind their annual Form 3. We are qualified and authorised to carry out fire safety maintenance and sign off SA council ESP Form 2 and Form 3 maintenance documentation.

Ask us for a sample report if you want to see the format before you book.

Who does the work

  • FPAS Recognised BusinessFire Protection Accreditation Scheme
  • FPA Australia Bronze MemberFire Protection Association Australia
  • Engineers AustraliaMember of the national body for engineers
  • CBS PGE fire plumbing licenceConsumer and Business Services SA
  • Licensed for electrical test and tagAS/NZS 3760 testing

All licences and certificates are held by suitably qualified personnel, and we are fully insured.

Frequently asked questions

What are the RCD test requirements in South Australia?
Under WHS regulation 165, a business with management or control of a workplace must take all reasonable steps to have its RCDs tested regularly by a competent person. A record of each test, other than daily push-button tests, must be kept until the RCD is next tested or permanently removed from use. A faulty RCD must be taken out of service.
When does a workplace have to use an RCD?
Regulation 164 requires an RCD where plug-in equipment is used in conditions likely to damage it, is moved between locations in a way that could damage it, is moved while operating, or is used with an amusement device. For outlets up to 20 A, the RCD must trip at 30 mA or less.
How often should RCDs be tested?
Regularly, by a competent person, with the interval set by your workplace's risk. SafeWork SA's guidance table gives separate intervals for the push-button test and the trip-time test. In factories and workshops, for example, it lists a trip-time test of portable and fixed RCDs every 12 months.
What is the difference between a push-button test and a trip-time test?
The push-button test checks that the RCD's mechanism trips. The trip-time test uses an instrument to check that it trips fast enough at its rated current. A switch can pass the push-button test and still be too slow, which is why both are done.
Can I test my own RCDs?
Anyone can press the test button, and doing so regularly is good practice. The regular testing required by regulation 165 must be done by a competent person, with the right instrument and a record of the result.
Do I need a record of RCD testing?
Yes, for everything except daily push-button tests. The record must be kept until the RCD is next tested or permanently removed from use. We give you a written record of every RCD we test.
Who is responsible for RCD testing in a shared building?
Regulation 165 puts the duty on the business with management or control of the workplace. In a shared building that can mean the landlord for common-area switchboards and each tenant for its own equipment and portable RCDs. Agree who covers what in writing.
What happens if an RCD fails?
It must be taken out of service and replaced as soon as possible. We label a failed portable RCD on the spot. A failed switchboard RCD needs a registered electrical worker to replace it.

Related guides

Get a quote for rcd testing

We send quotes the same day and call back within 15 minutes during business hours. Prefer to talk? Call 08 8151 1040.

No obligation. We only use your details to reply to this request.

Book your next service

Tell us what's on site and we'll send a fixed price the same day.

Call 08 8151 1040 Get a quote