Fire safety FAQs

The questions Adelaide building owners, landlords and providers ask us most, grouped by service.

Essential safety provisions (Form 3)

What is a Form 3 in South Australia?
Form 3 is the annual certificate a building owner gives council to confirm that the building's essential safety provisions have been maintained and tested as required. It is due within 60 business days after the end of each calendar year. PlanSA's current Form 3 template must be used from calendar year 2023.
Who is responsible for lodging the Form 3?
The building owner. The owner can use contractors to do the maintenance, and we sign the contractor section for the provisions we look after, but the obligation to lodge stays with the owner.
When is Form 3 due?
Within 60 business days after 31 December each year, for the calendar year just ended. Weekends and public holidays do not count, so the exact date moves a little each year. Check your council's ESP page for the date it is working to.
More about essential safety provisions (form 3)

Essential safety provisions (Form 2)

What is a Form 2 in South Australia?
Form 2 is the ESP compliance certificate. Regulation 94 of the Planning, Development and Infrastructure (General) Regulations 2017 says one must be provided for each essential safety provision listed on the building's Form 1 schedule, on completion of its installation.
Who signs the Form 2?
The person who installs the essential safety provision. If a company does the installation, a manager or other person responsible for managing the installation signs it. For the provisions we install, we sign it.
Where does the Form 2 go?
To the entity that will issue the certificate of occupancy for the building. If no certificate of occupancy is being issued, it goes to the council, or to the State Planning Commission outside council areas, within 20 business days after the provision is installed.
More about essential safety provisions (form 2)

Evacuation diagrams

Are evacuation diagrams a legal requirement in South Australia?
Every workplace must have an emergency plan under WHS regulation 43, and that plan must cover evacuation procedures. We found no SA law that names AS 3745 or mandates a particular diagram format. In practice, a clear diagram on the wall is one of the simplest ways to show workers and visitors how your evacuation procedure works.
What is the difference between an evacuation diagram and an evacuation plan?
The evacuation plan, or emergency plan, is the written document: who does what, how people get out, who calls emergency services and how the procedures are tested. The diagram is the picture of that plan for one spot in the building. You need the plan. The diagram helps people follow it.
Do I have to follow AS 3745?
AS 3745 is the Australian Standard for planning for emergencies in facilities and is widely used as best practice. No SA law we have found mandates it for every workplace. Some clients, insurers and contracts ask for it, so we lay out our diagrams with it in mind.
More about evacuation diagrams

Emergency management plans

Does every workplace in South Australia need an emergency plan?
Yes. Regulation 43 of the Work Health and Safety Regulations 2012 (SA) requires the person conducting a business or undertaking to have an emergency plan for the workplace. A small office needs one as much as a factory. The plan just needs to suit the size, hazards and people of the site.
What must an emergency plan include?
Emergency procedures, including an effective response, evacuation, notifying emergency services at the earliest opportunity, medical treatment and assistance, and communication between the person coordinating the response and everyone at the workplace. It must also cover how often the procedures are tested, and the information, training and instruction given to relevant workers.
Is AS 3745 mandatory in South Australia?
We have found no SA law that mandates AS 3745. It is the Australian Standard for planning for emergencies in facilities and is widely used as best practice, and SafeWork SA's code of practice points to it. Some insurers, head offices and contracts ask for it, so we lay out plans with it in mind.
More about emergency management plans

Fire extinguisher testing

How often do fire extinguishers need to be tested in South Australia?
Every 6 months. South Australia's maintenance instrument, MBS 002, calls up AS 1851-2012, which sets a 6-monthly inspection with a more thorough yearly service and a 5-yearly service. Your technician records each one on the extinguisher's tag and in your service report.
What happens at the 5-yearly service?
The extinguisher is emptied and checked internally, pressure tested where its type requires it, then refilled and re-tagged. If a unit fails, or costs more to recondition than to replace, we quote a replacement before doing anything.
Do I need my extinguishers serviced if my building doesn't lodge a Form 3?
Yes. Small buildings exempt from lodging a Form 3 must still maintain their essential safety provisions. Workplaces also have a general duty under the WHS laws to keep firefighting equipment in working order.
More about fire extinguisher testing

Fire extinguishers

Where can I buy a fire extinguisher in Adelaide?
Call us and tell us what the extinguisher is for. If you are buying for a workplace or a building with essential safety provisions, it is worth having the unit supplied and fitted by the same technician who will service it, so it is mounted, signed and on your service record from day one.
Do I need a technician to install a fire extinguisher?
In a workplace or a building that lodges a Form 3, extinguishers are part of the fire safety equipment that must be maintained to MBS 002, so a professional install gives you the first tag and a record to build on. For a home, you can mount one yourself. Read the manufacturer's instructions and keep it near an exit, not beside the stove.
How do I dispose of an old fire extinguisher in Adelaide?
Don't put a charged extinguisher in a household bin and don't try to empty it yourself. It is a pressurised container. Ask us about taking it away when we next visit.
More about fire extinguishers

Fire hose reel testing

How often do fire hose reels need to be tested in South Australia?
Every 6 months, with a more thorough yearly test. South Australia's maintenance instrument, MBS 002, calls up AS 1851-2012 for hose reels, and each test is recorded on the reel's tag and in your service report.
Who is allowed to test a fire hose reel in SA?
Testing firefighting equipment connected to mains water needs a test and inspect registration from Consumer and Business Services (CBS). The General and the Hydrant and hose reel categories both cover hose reels, and there is a Trainee category. We are FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your site.
Does hose reel testing need a plumber?
No. CBS requires plumbing registration for annual and longer tests on mains-connected firefighting equipment, but hose reels are the exception. A hose reel's yearly test needs the CBS test and inspect registration, not plumbing registration. Hydrants and sprinklers are different, so see those pages.
More about fire hose reel testing

Fire hydrant and booster testing

How often do fire hydrants need to be tested in South Australia?
Hydrant systems have routines that run from monthly to 5-yearly. South Australia's maintenance instrument, MBS 002, calls up AS 1851-2012, which sets what is checked at each interval. We set up the schedule for your system and record every visit.
What is a hydrant flow test?
A flow test runs water through the hydrant system and measures its flow and pressure, to confirm the system can still deliver what it was designed for. Because the system is connected to mains water, it needs a CBS test and inspect registration, and yearly and longer tests also need plumbing registration.
What is a fire booster assembly?
It is the set of inlets and valves, usually in a cabinet near the street, where the fire brigade connects its pumping appliance to boost the water pressure in your hydrant system. We check that it is accessible, signed, undamaged and that its valves and caps work.
More about fire hydrant and booster testing

Fire sprinklers, tanks and pumps

How often do fire sprinklers need to be serviced in South Australia?
Sprinkler systems are maintained to AS 1851-2012, which South Australia's MBS 002 calls up. Different parts of the system have different routines, so a sprinkler-protected building has some checks done often and others at longer intervals. We set up a schedule that covers every routine for your system and record each visit.
Who is allowed to test fire sprinklers in SA?
Testing firefighting equipment connected to mains water needs a test and inspect registration from Consumer and Business Services (CBS). Yearly and longer tests on sprinkler systems also need plumbing registration. We hold a CBS PGE fire plumbing licence and are FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your system.
Do you install fire sprinkler systems?
Yes. We install fire sprinkler systems as well as maintaining and testing existing ones, including fire pumps and tanks. Installation is quoted per project. Send us the building's plans and its Form 1 schedule and we will quote.
More about fire sprinklers, tanks and pumps

Fire alarm and detection testing

How often does a fire alarm system need to be tested in South Australia?
Fire detection and alarm systems have routines that run from monthly to 5-yearly. South Australia's maintenance instrument, MBS 002, calls up AS 1851-2012, which sets what is checked at each interval. We set up the schedule for your system and record every visit.
What is a fire indicator panel?
The fire indicator panel, or FIP, is the control panel for a building's fire detection system. It shows which detector or zone has gone into alarm, reports faults, and in a monitored system passes the alarm on. It is usually near the main entrance so the fire brigade can find it quickly.
Is this the same as smoke alarm testing for my house?
No. This page is about commercial detection systems run from a fire panel. Homes and rentals use standalone or interconnected smoke alarms under different rules. See our smoke alarms page for those.
More about fire alarm and detection testing

Smoke alarms

What smoke alarms does my home need in South Australia?
It depends on when the home was built. Homes built before 1 January 1995 need at least a battery smoke alarm. Homes built from 1 January 1995 need 240 V hardwired alarms, and new dwellings from 1 May 2014 need them interconnected. Different rules apply when a home is sold or transferred.
What are the smoke alarm rules when I buy a house?
Since 1 February 1998, when a home is sold or ownership is transferred, there are 6 months to fit hardwired smoke alarms or 10-year non-removable battery alarms. Fines of up to $750 apply. We can check the existing alarms and quote any upgrade soon after settlement.
Do landlords have to install smoke alarms in SA?
Yes. SA.GOV.AU states that "all rental properties must have a working smoke alarm installed." Check the alarms at every routine inspection, and book a technician for any that fail or are past their replace-by date. Our guide to smoke alarm rules for SA landlords covers the detail.
More about smoke alarms

Emergency and exit lighting

How often do emergency and exit lights need to be tested in South Australia?
Every 6 months and every year, with monthly checks in between. South Australia's maintenance instrument, MBS 002, calls up AS/NZS 2293.2 for emergency lighting and exit signs. Each test is recorded in your logbook and service report.
What happens during an emergency light test?
Mains power to the fittings is switched off so each light and exit sign runs on its battery. Our technician checks that every fitting comes on and stays lit for the time the standard requires, and records any that fail.
Who can do the monthly checks?
The monthly check sits between the formal tests and goes in your logbook. Ask us whether your own staff can do it, or whether to add it to your service plan.
More about emergency and exit lighting

Fire blankets

How often does a fire blanket need to be inspected in South Australia?
Every 6 months. South Australia's maintenance instrument, MBS 002, calls up AS 1851-2012, which sets a 6-monthly routine service for fire blankets. We usually inspect blankets on the same visit as your extinguishers, so one report covers both.
Does a kitchen need a fire blanket?
A fire blanket is one of the simplest ways to deal with a small fire in a pan of oil or fat. In a home, it is often the easiest first-aid firefighting tool to keep in the kitchen. In a workplace, the equipment you need depends on the hazards and on your building's Form 1 schedule if it has one. Commercial kitchens usually have a blanket alongside a wet chemical extinguisher.
Where should a fire blanket be mounted?
Near the cooking area but not right above or beside the stove, so you can reach it without leaning over the fire. On the path to the exit is a good choice: you grab the blanket on your way out of trouble, not into it. Mount it at a height everyone in the household or team can reach.
More about fire blankets

Fire doors and passive fire

How often do fire doors need to be inspected in South Australia?
Hinged fire doors are inspected every 6 months. South Australia's maintenance instrument, MBS 002 (version 3), calls up AS 1851-2012 for fire doors. Other door types and passive fire elements have their own routines, and we schedule each one on your plan.
What gets checked in a fire door inspection?
The door leaf, frame, hinges, door closer, latch and seals, plus the door's tag or label and any signage. The most important test is simple: open the door fully, let go, and confirm it closes and latches by itself with nothing holding it back.
Can a fire door be propped open?
Not with a wedge, a chair or a hook. A fire door only works if it is closed when the fire starts. If a door must stay open for daily use, it can be fitted with a hold-open device that releases it when the fire alarm operates. Ask us about the doors you need held open.
More about fire doors and passive fire

Fire safety inspections

What is checked in a fire safety inspection?
Every essential safety provision on your Form 1, such as extinguishers, hose reels, hydrants, detection and alarm systems, emergency and exit lighting and fire doors. We also check exits and paths of travel, signage, evacuation diagrams and the service records, and note anything overdue or faulty.
What is the difference between a fire safety inspection and a fire safety audit?
People use the terms loosely. For us, an inspection is a visual and functional check of your equipment on the day. An audit adds a check of your paperwork: the Form 1, service records and last Form 3, to find gaps before council or an insurer does.
How often do I need a fire safety inspection?
Your equipment has its own service intervals under MBS 002, from monthly to 5-yearly. A one-off inspection or audit makes most sense when you buy or take over a building, change contractors, receive a council or Building Fire Safety Committee notice, or want confidence before lodging Form 3.
More about fire safety inspections

Test and tag

How often do you need to test and tag in South Australia?
It depends on where the equipment is used. SafeWork SA's intervals are every 3 months on construction sites, every 6 months in manufacturing and commercial cleaning, at least every 12 months in other hostile environments, and at each hire and every 3 months for hire equipment. Lower-risk settings are set by a risk assessment, with AS/NZS 3760:2022 as guidance.
Is test and tag a legal requirement in SA?
For some equipment, yes. WHS regulation 150 requires plug-in equipment used in conditions likely to damage it, such as moisture, heat, vibration, mechanical damage, corrosive chemicals or dust, to be regularly inspected and tested by a competent person, with a record kept. For other equipment, you still have a general duty to manage electrical risks.
Does new equipment need to be tested and tagged?
New equipment that has not been used before does not need to be tested before first use under regulation 150, but it should be checked for obvious damage. It then joins your normal test cycle.
More about test and tag

RCD testing

What are the RCD test requirements in South Australia?
Under WHS regulation 165, a business with management or control of a workplace must take all reasonable steps to have its RCDs tested regularly by a competent person. A record of each test, other than daily push-button tests, must be kept until the RCD is next tested or permanently removed from use. A faulty RCD must be taken out of service.
When does a workplace have to use an RCD?
Regulation 164 requires an RCD where plug-in equipment is used in conditions likely to damage it, is moved between locations in a way that could damage it, is moved while operating, or is used with an amusement device. For outlets up to 20 A, the RCD must trip at 30 mA or less.
How often should RCDs be tested?
Regularly, by a competent person, with the interval set by your workplace's risk. SafeWork SA's guidance table gives separate intervals for the push-button test and the trip-time test. In factories and workshops, for example, it lists a trip-time test of portable and fixed RCDs every 12 months.
More about rcd testing

3 phase appliance testing

What is 3 phase appliance testing?
It is test and tag for equipment that plugs into a 3 phase outlet rather than a standard power point. The equipment is inspected, electrically tested and tagged, and the result is recorded, in the same way as single phase equipment but with test gear and methods suited to 3 phase.
Does 3 phase equipment need to be tested and tagged?
Yes, if it is plug-in equipment used in conditions likely to damage it. WHS regulation 150 covers equipment supplied through a socket outlet, which includes 3 phase plugs and sockets. Most 3 phase equipment is used in workshops, factories, kitchens and building sites, where that test applies.
How often should 3 phase appliances be tested?
The same intervals apply as for other plug-in equipment. SafeWork SA's intervals are every 3 months on construction sites, every 6 months in manufacturing, at least every 12 months in other hostile environments, and at each hire and every 3 months for hire equipment.
More about 3 phase appliance testing

SDA and NDIS homes

Does SDA have to be sprinklered?
Not always. The SDA Design Standard describes sprinklers as "desirable" but does not mandate them. Whether sprinklers are required depends on the building's NCC class. A Class 3 residential care building must be sprinklered throughout, and in SA a building counts as residential care when 10% or more of the residents need help to evacuate.
What fire safety does the SDA Design Standard require?
Edition 1.1, which applies to new SDA from 1 July 2021, requires the NCC fire safety provisions for the dwelling's building class, smoke alarms in bedrooms and living areas, and an evacuation plan given to the occupier. Anything more depends on the class your certifier gives the building.
How often should fire safety equipment in an SDA home be serviced?
We service SDA homes every 6 months. That matches the 6-monthly cycle South Australia's MBS 002 sets for extinguishers, fire blankets, emergency lighting and hinged fire doors, and it gives you two dated records a year for every home in your portfolio.
More about sda and ndis homes

Aged care

What fire safety systems does an aged care home need?
Most residential aged care homes are Class 9c buildings under the NCC. A Class 9c building needs sprinklers throughout, plus smoke detection connected to monitoring. It will also have exit and emergency lighting, fire doors, extinguishers and usually hose reels or hydrants. The full list for your building is on its Form 1 schedule of essential safety provisions.
Does an aged care home have to lodge a Form 3?
Plan on it. MBS 002 exempts Class 1b buildings, and Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less. Class 9c is not in that list. The owner lodges the Form 3 with council within 60 business days after the end of each calendar year. We supply the maintenance records behind it and sign the contractor section.
What does outcome 2.10 of the strengthened Quality Standards require?
Outcome 2.10 covers emergency and disaster management. It requires emergency plans that are regularly tested. Fire is the emergency most homes plan for first, so evacuation drills, a current evacuation diagram and working fire systems are all part of the evidence an assessor may ask for.
More about aged care

Landlords and property managers

What are the smoke alarm rules for rental properties in South Australia?
All rental properties must have a working smoke alarm installed. What type is needed depends on when the home was built and whether it has changed hands: homes built from 1 January 1995 need 240 V hardwired alarms, new dwellings from 1 May 2014 need them interconnected, and a home bought since 1 February 1998 needs hardwired or 10-year non-removable battery alarms within 6 months of transfer.
Who is responsible for smoke alarms in a rental, the landlord or the tenant?
The rule is that all rental properties must have a working smoke alarm installed. In practice the landlord arranges it, usually through the property manager, and SA.GOV.AU advises checking alarms at routine inspections. Tenants should report an alarm that chirps, fails its test button or has been removed.
Can a property manager replace a hardwired smoke alarm?
No. Hardwired smoke alarm work needs a registered electrical worker, who must issue an electronic Certificate of Compliance. A property manager can press the test button at an inspection, but replacing or rewiring a hardwired alarm is electrical work.
More about landlords and property managers

Strata and apartments

Who is responsible for fire safety in a strata building?
The corporation looks after the common property. Under the Strata Titles Act 1988 it must administer and maintain the common property, and under the Community Titles Act 1996 it must keep the common property in good order and condition. Most of a building's fire safety systems, such as exit lighting, hydrants, hose reels and stairwell fire doors, sit on common property. Owners look after what is inside their own unit or lot.
Does every strata building need a Form 3?
Every Class 2 apartment building needs one. MBS 002 exempts only Class 1b buildings and small Class 3 to 9b buildings, so Class 2 is not exempt. The Form 3 is lodged with council within 60 business days after the end of each calendar year. Townhouse groups made up of Class 1a houses are outside the scheme.
Who signs the Form 3 for a strata building?
The owner of the building's essential safety provisions, which for common-property systems is the corporation, usually acting through its strata manager. We don't take the Form 3 over. We supply the maintenance records for the year and sign the contractor section for the work we did.
More about strata and apartments

Construction sites

How often does construction equipment need to be tested and tagged in SA?
Every 3 months. SafeWork SA sets a 3-monthly interval for electrical equipment used in construction, compared with 6 months for manufacturing and at least every 12 months for other hostile environments. Hire equipment is tested at each hire and every 3 months.
Does a construction site need fire extinguishers?
Every workplace must plan for emergencies, and a site's fire risk changes as the build goes on: hot work, fuel, gas bottles, switchboards and stacked materials. Extinguishers matched to those hazards, placed where workers can reach them and kept serviced, are part of managing that risk. We help you choose the types and locations.
Does a construction site need an emergency plan?
Yes. WHS regulation 43 requires an emergency plan for every workplace, and a construction site is a workplace. AS 3745 is best practice for emergency planning, but we have found no SA law that mandates it.
More about construction sites

Commercial offices

What fire safety does an office need in South Australia?
It depends on the building. Most offices have portable extinguishers, exit and emergency lighting, and fire doors. Larger buildings add detection and alarm systems, hose reels, hydrants and sometimes sprinklers. The full list for your building is on its Form 1 schedule of essential safety provisions. Every workplace also needs an emergency plan under WHS regulation 43.
Does my office building need to lodge a Form 3?
Most commercial buildings do. Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less are exempt from lodging, unless a section 157 notice or a performance solution applies. Exempt owners must still maintain their essential safety provisions.
Who is responsible for fire safety in a leased office, the landlord or the tenant?
Both have duties. The building owner must maintain the essential safety provisions and lodge the Form 3. Each tenant, as a business, must have an emergency plan for its workplace and keep its own equipment safe. Leases often split the maintenance costs, so check yours and agree who books what.
More about commercial offices

Industrial and warehouses

What fire safety equipment does a warehouse need?
It depends on the building's size, class and what is stored in it. Most warehouses have portable extinguishers, hose reels, exit lighting and hydrants. Many larger ones also have sprinklers, detection and fire water tanks with pumps. The building's Form 1 schedule of essential safety provisions lists exactly what yours has.
How often are fire hydrants tested in a warehouse?
Hydrant systems are serviced on schedules that run from monthly to 5-yearly under MBS 002, depending on the component and the test. Testing equipment connected to mains water needs CBS test and inspect registration, and annual and longer tests need plumbing registration.
How often does equipment in a factory need to be tested and tagged?
SafeWork SA sets 6-monthly testing for electrical equipment in manufacturing, and at least every 12 months in other hostile environments, where equipment is exposed to moisture, heat, vibration, damage, chemicals or dust.
More about industrial and warehouses

Schools and childcare

How often must a childcare centre rehearse its evacuation procedures?
Every 3 months. ACECQA's guidance under the Education and Care Services National Regulations says emergency and evacuation procedures must be rehearsed and documented every 3 months. In South Australia, the Education Standards Board expects one evacuation and one invacuation rehearsal every 3 months.
What is an invacuation?
An invacuation, or lockdown, moves children and staff into a safe area inside the building instead of outside, for example when the danger is outside. Services plan and rehearse it alongside evacuation.
How often should a childcare centre review its emergency risk assessment?
The Education Standards Board says a service must review its potential emergencies risk assessment every 12 months, and as soon as practicable after becoming aware of anything that may affect the safe evacuation of children.
More about schools and childcare

Homes

What smoke alarms does my home need in South Australia?
It depends on when the home was built. Homes built before 1 January 1995 need at least a battery smoke alarm. Homes built from 1 January 1995 need 240 V hardwired alarms. New homes from 1 May 2014 need interconnected alarms, so when one sounds they all sound.
What do I need to do about smoke alarms when I buy a home?
Since 1 February 1998, when a home is sold or transferred, the new owner has 6 months to fit hardwired smoke alarms or 10-year non-removable battery alarms. Fines of up to $750 apply.
What is the best fire extinguisher for a home?
For the kitchen, a fire blanket is often the simpler choice. For the rest of the home, a small dry powder extinguisher rated for Class A, B and E fires is a common choice. Keep it near an exit, not beside the stove.
More about homes

Hospitality and retail

What fire extinguisher does a commercial kitchen need?
A wet chemical extinguisher, the type made for cooking oil and fat fires (Class F). Most commercial kitchens also have a fire blanket. Front of house and the switchboard usually need a different type, such as powder or CO2.
Can you use water on a deep fryer fire?
No. Water on burning oil or fat makes the fire erupt. Fire protection guidance rates water extinguishers as dangerous on cooking oil and fat fires. Use a wet chemical extinguisher or a fire blanket, turn off the heat if it is safe to, and leave and call 000 if it doesn't go out.
Do you service kitchen fire suppression systems?
Ask us. Tell us the make of the fixed system above your cooking line and we'll confirm whether we can service it.
More about hospitality and retail

Healthcare and medical

What fire safety does a medical centre need?
It depends on the building's class, size and use, which are set at approval. Most clinics have portable extinguishers, exit and emergency lighting and fire doors. Larger buildings and day hospitals add detection, alarms and often sprinklers. The building's Form 1 schedule of essential safety provisions lists what it has.
Does a medical centre have to lodge a Form 3?
Most do. Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less are exempt from lodging, unless a section 157 notice or a performance solution applies. Exempt owners must still maintain their essential safety provisions.
How do clinics plan for patients who can't evacuate on their own?
The emergency plan should name who helps each kind of patient: people in treatment chairs, under sedation, on mobility aids or with hearing or vision loss. Where the building is divided into fire compartments, moving patients to the next compartment may be safer than taking them outside.
More about healthcare and medical

Book your next service

Tell us what's on site and we'll send a fixed price the same day.