Fire safety on common property is the corporation’s job
In a strata or community title building, the fire safety systems that protect everyone usually sit on common property: the exit signs and emergency lights in the corridors, the stairwell fire doors, the hydrants and hose reels, the fire detection system and the extinguishers in the car park.
South Australian law puts the maintenance of common property on the corporation. Under the Strata Titles Act 1988, the strata corporation must administer and maintain the common property for the benefit of all unit holders. Under the Community Titles Act 1996, the community corporation must maintain the common property in good order and condition. Fire safety systems on common property are part of that duty.
We work for the corporation, usually through its strata manager, to keep those systems serviced, fix what fails and keep the records that prove it.
Form 3 for every Class 2 building
Apartment buildings are Class 2 under the National Construction Code. South Australia’s maintenance standard, MBS 002, exempts only Class 1b buildings and Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less. Class 2 is not on that list, so every Class 2 building lodges a Form 3.
The Form 3 is the owner’s annual certificate to council that the building’s essential safety provisions (ESPs) have been maintained. It is lodged within 60 business days after the end of each calendar year. The list of ESPs it covers is the building’s Form 1 schedule, issued at approval.
Form 3 stays the owner’s obligation. For the corporation, we:
- service every ESP on your Form 1 schedule on its MBS 002 frequency
- record each service, with defects and when they were fixed
- sign the contractor section of the Form 3 for the work we did
- send the strata manager a year-end pack in January, well before the 60-business-day deadline
Councils cite $750 expiations for not lodging or not maintaining, and up to $10,000 if prosecuted. Building Fire Safety Committees can issue s157 notices. See essential safety provisions and Form 3.
What a typical Adelaide apartment building has
| System | Where you’ll find it | How often it’s serviced |
|---|---|---|
| Exit and emergency lighting | Corridors, stairs, car park | 6-monthly and yearly, plus monthly checks |
| Fire doors | Stairwells and corridor separations | Hinged fire doors every 6 months |
| Apartment entrance smoke doors | The front door of each apartment | On the AS 1851-2012 schedule for the door type |
| Hose reels | Car park and plant areas | 6-monthly and yearly |
| Hydrants and boosters | Street frontage and stair landings | Monthly to 5-yearly |
| Fire detection and alarm | Common areas, plant rooms, car park | Monthly to 5-yearly |
| Extinguishers | Car park, bin room, plant rooms | Every 6 months, plus yearly and 5-yearly |
Testing firefighting equipment connected to mains water needs CBS test and inspect registration. We hold a CBS PGE fire plumbing licence and are FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your building.
Apartment entrance smoke doors
The front door of each apartment is often a smoke door. It is meant to close by itself and seal well enough to keep smoke in the apartment where a fire starts, or out of the corridor everyone uses to escape.
They are also the doors residents most often change. A new handle, a removed closer, a pet flap, a gap under the door after new flooring, or a door wedged open in summer can all stop a smoke door working. Because the door sits between the unit and the common property, check your by-laws to see who pays to fix it. We record each door’s condition by unit number, so the strata manager can send the right notice to the right owner.
Each door check covers:
- the door closes and latches by itself from any open position
- smoke seals are present, continuous and undamaged
- gaps at the head, sides and threshold are within limits
- hinges, closer and latch are in working order
- no alterations that affect the door’s performance
Problems we often see in apartment buildings
Most fire safety defects in strata buildings are not equipment failures. They come from how the building is used. These are the things we check for on every visit:
- Fire doors wedged open in stairwells and bin rooms, or fitted with door stops that defeat the closer.
- Exit signs and emergency lights out because a battery or lamp has failed and no one reported it.
- Hose reels blocked by stored bikes, boxes or furniture in the car park.
- Extinguishers missing or discharged in car parks and bin rooms.
- Penetrations left open after a contractor has run new cabling or pipes through a fire-rated wall.
- Entrance doors altered by residents, with closers removed or new hardware fitted.
Each one is listed in the report with its location, so the strata manager can fix it or send a notice to the right owner.
Building Fire Safety Committees and s157 notices
Councils have Building Fire Safety Committees that can inspect buildings and issue s157 notices requiring fire safety work to be done. A notice can also bring a building that would otherwise be exempt into the Form 3 scheme. If your corporation has received one, send it to us with your Form 1 schedule. We will set out what the notice asks for, quote the work we can do, and keep the records you need to show it was done.
Evacuation diagrams for apartment buildings
AS 3745 is the best-practice standard for evacuation diagrams and emergency planning, but we have found no SA law that mandates it for apartment buildings. Many corporations still display diagrams in corridors and lift lobbies, because residents and visitors need to know where the exits and hydrants are. We can prepare them to AS 3745 and update them when the building changes. See evacuation diagrams.
Working with strata managers
Strata managers juggle dozens of buildings. We make fire safety one less thing to chase.
- One schedule per building. Every ESP, every due date, every visit booked in advance.
- Notices for residents. We supply a short notice for the strata manager to send before alarm tests or door rounds.
- Quotes for approval. Defects come with a written quote, so the committee can approve repairs quickly.
- Records in one place. Each visit’s report, plus the year-end Form 3 pack.
We can also check smoke alarms inside units on the same visit, billed to each owner, if the corporation agrees. Unit alarms are usually the owner’s responsibility. For rented units, see our landlords and property managers page.
New buildings and handover
When a developer hands a new building to the corporation, the first year of ESP maintenance starts straight away. We can take the building on at handover, check the Form 1 schedule against what is installed, and set up the first year’s service plan so the first Form 3 is complete.
The rules that apply
| Requirement | What it means | Standard | SA source |
|---|---|---|---|
| Common property (strata scheme) | Ongoing duty | The corporation must administer and maintain the common property (Strata Titles Act 1988 s 25) | SA Law Handbook |
| Common property (community scheme) | Ongoing duty | The corporation must maintain the common property in good order and condition (Community Titles Act 1996 s 75(1)(b)) | SA Law Handbook |
| Annual Form 3 (ESP maintenance certificate) | Within 60 business days after the end of each calendar year | Class 2 buildings are not among the exempt classes | PlanSA Form 3, MBS 002 v3 |
| Hinged fire doors | Every 6 months | AS 1851-2012 | MBS 002 v3 (SA) |
| Apartment entrance smoke doors | The routine AS 1851-2012 sets for the door type | AS 1851-2012 | MBS 002 v3 (SA) |
| Emergency and exit lighting | 6-monthly and yearly, plus monthly checks | AS/NZS 2293.2 | MBS 002 v3 (SA) |
| Hose reels | 6-monthly and yearly | AS 1851-2012 | MBS 002 v3 (SA) |
| Hydrants and fire detection systems | Monthly to 5-yearly | AS 1851-2012 | MBS 002 v3 (SA) |
| Portable extinguishers | Every 6 months, plus yearly and 5-yearly | AS 1851-2012 | MBS 002 v3 (SA) |