Fire water tanks and sprinkler systems in South Australia are serviced on AS 1851-2012 schedules, which MBS 002 calls up, from frequent routine checks through 6-monthly and yearly services to longer tests such as 3-yearly sprinkler tests. Because they connect to mains water, the tester needs a CBS test and inspect registration, plus a plumbing registration for annual and longer tests.
These systems sit out of sight in plant rooms, basements or on the roof, and a fire is the wrong time to find out whether the tank is full and the sprinklers will deliver.
That’s why fire tank and sprinkler inspection is part of the routine servicing schedule for commercial, industrial and multi-residential buildings that have these systems. VD Fire & Electrical works on fire protection systems across Adelaide, and people ask the same things: what’s involved, how often it needs doing, and how the tank, sprinklers and fire panel fit together.
What fire tanks and sprinklers do, and how they fail
A fire water tank stores a dedicated supply of water for your fire protection systems, such as sprinklers, hydrants and hose reels, so water is available even if the mains supply is interrupted or can’t keep up. Sprinklers use that water to control a fire automatically, often before anyone has noticed it.
Both rely on things that can fail quietly: a falling water level, a corroded fitting, a closed valve or a damaged sprinkler head. A tank that looks fine from the outside can still be low or contaminated, which is why fire tank inspections are scheduled and hands-on rather than left to chance.
How often fire tanks are inspected
South Australia’s maintenance standard is MBS 002 (version 3, May 2023). It calls up AS 1851-2012, the Australian Standard for routine service of fire protection systems and equipment. Its schedules run from frequent routine checks through 6-monthly and yearly services to tests at longer intervals, such as the 3-yearly sprinkler tests that Consumer and Business Services mentions.
The exact tasks depend on the type of system, so we confirm the schedule for each site against your building’s Form 1, the schedule of essential safety provisions.
Who can test fire sprinklers and tanks in SA
Sprinkler systems and tanks connected to mains water are licensed work in South Australia. According to Consumer and Business Services, testing needs a CBS test and inspect registration, and annual or longer tests, such as 3-yearly sprinkler tests, also need a plumbing registration that covers the work.
VD Fire & Electrical holds a CBS PGE fire plumbing licence and is FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your system.
What fire tank inspections in Adelaide involve
A typical inspection of a fire water tank includes:
- Checking the tank, supports and surrounding area for leaks, corrosion and damage.
- Confirming the water level, and that the inlet and make-up supply are working.
- Inspecting valves, outlets and connections, and checking they’re in the correct position.
- Checking level gauges and alarms.
- Checking the roof, hatches and vents are secure and sealed against vermin.
- Checking water condition and any sediment build-up.
- Recording the results and any defects.
Fire sprinkler testing and fire panel testing in Adelaide
Sprinkler testing and fire panel testing are closely linked, because the panel is how a sprinkler activation is reported. A service typically covers:
- Checking control valves are open and secured, and that gauges show normal pressure.
- Testing alarm valves and flow alarms.
- Inspecting sprinkler heads for damage, corrosion, paint or obstruction.
- Confirming nothing is stored close enough to block the sprinkler spray.
- Run-testing pumps, where fitted.
- Checking that sprinkler flow and valve signals reach the fire indicator panel.
- Testing the panel itself, including fault and alarm signals.
Fire detection and alarm systems have their own schedule under MBS 002, from monthly to 5-yearly. Doing these together gives a complete picture of whether the system will respond as designed, and one set of records to show for it. If you’d like your tank, sprinklers and fire panel checked in one visit, request a quote and we’ll scope it with you.
Compliance requirements and standards for fire tanks and sprinklers
AS 1851-2012, through MBS 002, covers routine servicing of both systems. How they’re designed and installed is covered by other standards, such as AS 2118.1 for sprinklers. Your building’s approval documents and Form 1 set out whether these systems are required in the first place.
Service reports are the other half of compliance. Keep them on file, and make sure any defects found have been recorded and fixed. They are the evidence behind the owner’s annual Form 3, lodged with council within 60 business days after the end of each calendar year. Not lodging or not maintaining ESPs carries a $750 expiation and a maximum penalty of $10,000 under regulation 94 of the Planning, Development and Infrastructure (General) Regulations 2017. A lapse here matters more than most, because other systems depend on the same water supply.
One more rule worth knowing: Class 3 residential care buildings and Class 9c aged care buildings must be sprinklered throughout under the NCC (see our aged care and SDA and NDIS pages).
Signs your fire tank or sprinklers need attention sooner
- A water level that has dropped, or keeps dropping, without explanation.
- Leaks, rust, flaking paint or visible corrosion on the tank or pipework.
- Discoloured or dirty water, or sediment in the tank.
- Sprinkler heads that are damaged, corroded or painted over.
- Stock or fittings stacked close to sprinkler heads.
- Fault or warning lights on the fire panel.
Any of these is a reason to arrange an inspection early rather than wait for the next scheduled visit.
Everything else in your fire protection depends on the tanks and sprinklers. Keep them on a regular schedule, keep the records tidy, and they’ll be ready. If you’re not sure when yours were last inspected, call VD Fire & Electrical on 08 8151 1040 and we’ll help you find out, or see fire sprinkler testing. Hydrant systems are covered in our guide to fire hydrant inspections.