Fire safety for SDA starts with the building class
The fire safety an SDA or SIL home needs is set by its National Construction Code (NCC) building class, not by the SDA category alone. Your building certifier decides the class at approval. PlanSA’s Advisory Notice 01/24 explains how buildings for unrelated residents with care needs are classified in South Australia.
The SDA Design Standard (edition 1.1, which applies to new SDA from 1 July 2021) sits on top of the NCC. It requires the NCC fire safety provisions for the dwelling’s class, smoke alarms in bedrooms and living areas, and an evacuation plan given to the occupier. It describes fire sprinklers as “desirable” but does not mandate them.
| Building class | Typical SDA setting | What it means for fire safety |
|---|---|---|
| Class 1a | A house or villa | Outside the essential safety provisions (ESP) scheme, so no Form 3. The SDA Design Standard still needs smoke alarms in bedrooms and living areas and an evacuation plan. |
| Class 1b | A small boarding house or shared home | Exempt from lodging a Form 3, but the owner must still maintain every ESP that was required at approval. |
| Class 2 | SDA apartments in a larger building | Not exempt from Form 3. Common-area systems are usually the strata corporation’s job. The dwelling itself is yours. See our strata page. |
| Class 3 | A larger shared home or supported accommodation | Exempt from lodging only if the rise is 2 storeys or less and 500 m² or less, with no s157 notice or performance solution. If it is a residential care building, it must be sprinklered throughout. |
In South Australia, a building is treated as a residential care building when 10% or more of the people who live there need help to evacuate. That threshold matters when residents’ needs change. A Class 3 home that was not residential care when it was approved may need its classification reviewed if more residents now need physical help to get out.
Building or buying? NCC 2022 applies in South Australia until 30 April 2027, and NCC 2025 starts on 1 May 2027. Check which edition your approval falls under.
Why SDA fire safety needs more care
The NDIS Commission’s fire safety alert notes that disability is a factor in about 62% of preventable home fire deaths. Many SDA residents cannot hear a standard alarm, cannot get out of bed unaided, or need a support worker to guide them out. A house that passes a basic smoke alarm check can still leave those residents at risk.
That is why we plan each home around the people who live in it: how they will be woken, who will help them, and which way they will leave.
Fire risk assessments
We carry out fire risk assessments for SDA and SIL homes. We walk through the home, check what is installed against its building class and the SDA Design Standard, look at the exits and the paths to them, and talk to staff about the residents who need help to get out. You get a written report of what is in place, what is missing and what needs fixing, which becomes the starting point for the move-in package. See our fire safety inspections and audits page. The first fire safety audit is free.
Installation and maintenance of fire safety systems
We install and maintain the fire safety systems an SDA or SIL home relies on: smoke detectors, fire alarms, extinguishers, hydrants and emergency lighting. Hardwired electrical work is done by our licensed electrical contractor. New work and upgrades are quoted per property, and once a system is in we keep it on the same service schedule as the rest of your portfolio.
The move-in package
Before a new resident moves in, or when a home changes hands between providers, we set the home up and document it.
- Interconnected photoelectric smoke alarms. Every alarm sounds when one detects smoke, so a resident in a far bedroom hears a fire in the kitchen. MFS recommends photoelectric alarms hard-wired to the 240 V supply. We supply and install them. Hardwired work is done by our licensed electrical contractor, who issues an electronic Certificate of Compliance.
- Strobe or vibrating alarms for residents with hearing loss. MFS notes that specialised systems add strobe lights and vibrating elements to the audible alarm. We fit them in the bedrooms that need them and link them to the main alarms.
- A resident-specific evacuation plan. The SDA Design Standard requires an evacuation plan given to the occupier. We write it for the actual residents: how each person is alerted, who assists them, the exit route and the assembly point. We can add an evacuation diagram for the wall.
- Emergency power for powered equipment. If a resident relies on powered equipment, ask us about checking the home’s emergency power solution.
- Fire extinguisher and fire blanket. We supply, mount and tag a fire extinguisher and a fire blanket near the kitchen, and show staff where they are.
You get a move-in report for the property file: what was installed or checked, where, its test result, and a copy of the evacuation plan.
6-monthly servicing
After move-in, we service every home in your portfolio every 6 months. South Australia’s maintenance standard, MBS 002, sets a 6-monthly cycle for extinguishers, fire blankets, emergency lighting and hinged fire doors, so one visit covers most of what an SDA home has.
At each visit we:
- test every smoke alarm, including interconnection and any strobe or vibrating devices
- inspect and tag the extinguisher and fire blanket (extinguisher testing)
- test emergency and exit lighting where the home has it (exit lighting testing)
- check exit doors open easily, paths are clear and the evacuation plan is still on display
- ask staff whether residents’ needs have changed, and flag the plan for review if they have
Homes in larger buildings may also have detection systems or sprinklers. We service those on their own MBS 002 schedules (fire alarm testing, sprinkler testing). We hold a CBS PGE fire plumbing licence and are FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your building.
Records ready for NDIS Commission audits
The NDIS Practice Standards require providers to have emergency plans that are tested and reviewed, with every worker trained in them. Auditors look for evidence. We make that evidence easy to produce.
- One record per property. Every visit ends with a dated report listing each item, its location and its result.
- Defects tracked to close-out. Anything that fails is listed with what we did or quoted, so you can show it was fixed.
- Evacuation plan reviews. The date each plan was last reviewed, and what changed.
- Portfolio summary. One report across every home, so a quality manager can see what is due before the auditor asks.
- ESP logbooks. Where a home has essential safety provisions, each visit is entered in its logbook as well as the report.
For buildings that must lodge a Form 3, the owner still signs and lodges it with council within 60 business days after the end of each calendar year. We supply the maintenance records behind it and sign the contractor section. See Form 3 and essential safety provisions.
Staff fire training
Every worker needs to know the plan: the alarm, the route, where residents gather and who helps whom. Staff learn it best in the home itself, on the real route with the real equipment. We write the emergency plan and evacuation diagrams your staff train on, and keep the equipment they would use working.
Portfolio pricing
SDA and SIL providers rarely have one home. We price a portfolio per property, put every home on one service schedule, and send one consolidated report.
Each home is quoted once we know its building class and what is installed. Send us your list of homes and ask us for a portfolio quote.
Working with your team
We liaise with whoever needs to be involved. The provider books the work. The house manager gives us access and tells us about the residents. The support coordinator or OT tells us what alerting and assistance each person needs. The builder gets a handover check before the first resident moves in. Everyone gets the documents they need, with the provider’s agreement.
The rules that apply
| Requirement | What it means | Standard | SA source |
|---|---|---|---|
| Fire safety for the dwelling | New SDA enrolled from 1 July 2021 | SDA Design Standard edition 1.1 requires the NCC fire safety provisions for the dwelling's building class | NDIS SDA Design Standard |
| Smoke alarms | In bedrooms and living areas | SDA Design Standard edition 1.1 | NDIS SDA Design Standard |
| Evacuation plan | Given to the occupier | SDA Design Standard edition 1.1 | NDIS SDA Design Standard |
| Fire sprinklers in SDA | Described as "desirable", not mandated | SDA Design Standard edition 1.1 | NDIS SDA Design Standard |
| Class 3 residential care buildings | Sprinklered throughout | NCC 2022 Volume One, Part E1 | ABCB NCC 2022 |
| What counts as residential care in SA | 10% or more of residents need help to evacuate | Advisory Notice Building 01/24 | PlanSA |
| NDIS provider emergency plans | Tested and reviewed, with every worker trained | NDIS Practice Standards, emergency and disaster management | NDIS Commission |
| Extinguishers and fire blankets | Every 6 months (extinguishers also yearly and 5-yearly) | AS 1851-2012 | MBS 002 v3 (SA) |
| Emergency and exit lighting | 6-monthly and yearly, plus monthly checks | AS/NZS 2293.2 | MBS 002 v3 (SA) |