The SDA Design Standard requires NCC fire safety for the dwelling’s class, smoke alarms in bedrooms and living areas, and an evacuation plan for the occupier, and it calls sprinklers desirable rather than mandatory. Whether sprinklers are required comes from the National Construction Code (NCC), and a Class 3 residential care building must have them throughout.
Most confusion about SDA fire safety comes from mixing those two rulebooks up, so it helps to take them one at a time.
For the full service picture, see our SDA and NDIS fire safety page.
What the SDA Design Standard requires
The SDA Design Standard edition 1.1 applies to new SDA from 1 July 2021. On fire safety, it requires:
- NCC fire safety for the dwelling’s class. The Design Standard doesn’t write its own fire rules. It requires the NCC fire safety provisions that apply to the building’s class.
- Smoke alarms in bedrooms and living areas.
- An evacuation plan given to the occupier.
It describes fire sprinklers as “desirable”. Desirable is not mandatory.
Sprinklers depend on the building class
Whether an SDA building needs sprinklers is decided by the NCC, based on its class:
| Building | Sprinklers |
|---|---|
| Class 3 residential care building | Required throughout (NCC 2022 Part E1, E1D7) |
| Other SDA, under the Design Standard alone | “Desirable”, not mandated |
So “SDA must be sprinklered” is wrong as a blanket statement, and so is “SDA never needs sprinklers”. Check the building’s class, and check it again when residents’ needs change.
The SA residential care test
PlanSA’s Advisory Notice Building 01/24 covers how South Australia classifies residential buildings for unrelated residents with care needs. The NCC defines a residential care building as a Class 3, 9a or 9c building where 10% or more of the residents need physical assistance with daily activities and to evacuate in an emergency.
That threshold can change without any building work. A Class 3 home that wasn’t residential care can become one as residents age, their needs increase or the resident mix changes. If it does, it must be sprinklered throughout. Providers should review classification whenever residents move in or their support needs change.
Building classes you’ll see in SDA
| Class | Typical SDA | Form 3 |
|---|---|---|
| Class 1a | A house or villa | Outside the ESP scheme |
| Class 1b | A small shared home or boarding house | Exempt from lodging, but ESPs must still be maintained |
| Class 2 | An apartment in a larger building | Not exempt. Common areas are often run by the strata corporation |
| Class 3 | A larger shared home or supported accommodation | Exempt only if a rise of 2 storeys or less and 500 m² or less, with no s157 notice or performance solution |
The Form 3 is the owner’s annual certificate to council, lodged within 60 business days after the end of each calendar year. See essential safety provisions and Form 3.
Smoke alarms
Smoke alarms in bedrooms and living areas are a Design Standard requirement. For SDA we recommend interconnected photoelectric alarms, so an alarm in one room sounds in all of them. The MFS notes that alarms with strobe lights and vibrating elements are available for people who are deaf or hard of hearing. Our guides to interconnected smoke alarms and photoelectric and ionisation alarms explain the choices. Hardwired smoke alarm work needs a registered electrical worker, who issues an electronic Certificate of Compliance. See smoke alarms.
The evacuation plan
The Design Standard requires an evacuation plan given to the occupier. A plan for an SDA resident should be specific to them: how they will know there is a fire, how they will get out, who helps and how, and where they go. It should match the evacuation diagram and be easy for the resident and support workers to follow. See evacuation diagrams.
NDIS provider obligations
Providers registered with the NDIS Commission must meet the NDIS Practice Standards, which require emergency plans that are tested and reviewed, with every worker trained. The NDIS Commission’s fire safety alert notes that disability is a factor in about 62% of preventable home fire deaths.
Maintenance after move-in
Whatever the class, the equipment in an SDA home has to be maintained. Extinguishers are serviced every 6 months under AS 1851-2012, which South Australia’s MBS 002 calls up, with yearly and 5-yearly services on top. Emergency lighting, where fitted, is serviced 6-monthly and yearly with monthly checks.
Code changes
NCC 2022 applies in South Australia until 30 April 2027, and the building provisions of NCC 2025 start on 1 May 2027 (PlanSA). If you are designing or building SDA now, check which code edition your approval falls under.