Fire door inspections and passive fire protection in Adelaide

We inspect fire doors and the passive fire protection around them, so the walls, doors and seals that hold back fire and smoke still do their job. Hinged fire doors are inspected every 6 months under South Australia's MBS 002, and inspections are quoted per site on the number of doors.

Why fire doors matter

Most buildings bigger than a house are divided into fire compartments. The walls, floors and doors between them are built to hold back fire and smoke for a set time, so people can get out and firefighters can work. A fire door is the weak point in that wall, because people open it hundreds of times a day.

A fire door does nothing if it is wedged open, if the closer is too weak to latch it, or if the seals have been torn off. Those faults are common, easy to miss and quick to fix. That is what the 6-monthly inspection is for.

What we inspect on each fire door

We inspect hinged fire doors every 6 months, as MBS 002 requires, and report each one by location so your maintenance staff can find it. On each door we check the leaf and frame, hinges, closer, latch and seals, any hold-open device, and the door’s tag and signs. Then we open it fully, let go, and confirm it closes and latches by itself.

The common faults

Most of the defects we find on fire doors have nothing to do with age. They are the result of daily use:

  • Wedged or hooked open. The most common fault, and the most dangerous.
  • Closer adjusted to “soft”. Someone found the door heavy, so the closer was turned down until it no longer latches.
  • Seals removed. Smoke seals pulled off because the door “stuck”.
  • New hardware. Extra locks, kick plates, peepholes or vision panels fitted without checking the door’s rating.
  • Holes. Old hardware removed and the screw holes or cut-outs left open.
  • Furniture in the swing. A bin, trolley or chair that stops the door closing.

Each defect goes in your report with its location and a recommended fix, so you can approve the work and close it out before your Form 3.

Passive fire protection and fire stopping

Fire doors are only part of passive fire protection. The rest is in the walls, floors and ceilings themselves, and the biggest risk is every hole a trade has ever cut through them. A data cable run through a fire wall, a new pipe through a slab, or a duct through a ceiling can each open a path for smoke and fire unless the gap is sealed with a tested fire stopping system.

Because penetrations are often hidden above ceilings and inside risers, they are easy to lose track of after a fit-out. During our inspections we look for:

  • unsealed or poorly sealed penetrations in fire-rated walls, floors and risers we can access
  • cables or pipes added through existing seals after the seal was installed
  • damage to fire-rated walls and ceilings, such as removed panels and holes
  • missing identification labels on fire stopping, where the system uses them

Tell us what you want checked, including any ceiling spaces and risers, and we’ll confirm the scope before the visit.

Repairs and remediation

Ask us about repairs to the defects in your report. Whoever does the work, a repair to a fire door or a fire-rated wall should use parts and systems that match the element’s rating, and the record should show what was done, where and when.

Fire doors and your Form 3

Fire doors are usually on a building’s Form 1 schedule of essential safety provisions. The owner lodges a Form 3 with council within 60 business days after the end of each calendar year, certifying that those provisions were maintained. Our fire door reports are the maintenance records behind it. We supply them and sign the contractor section for the work we did, but the Form 3 stays the owner’s obligation.

Class 1b buildings, and Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less, are exempt from lodging unless a section 157 notice or a performance solution applies, but exempt owners must still maintain their essential safety provisions. Councils cite $750 expiations for not maintaining them, and up to $10,000 if prosecuted. See essential safety provisions and Form 3.

Fire doors in care and multi-storey buildings

In aged care homes and hospitals, fire and smoke doors let staff move residents and patients into the next compartment instead of out of the building. Those doors take a beating from beds, lifters and trolleys, so faults appear fast. In apartment buildings, the doors between corridors, stairs and units hold back smoke from the escape route. See aged care, strata and healthcare.

How we work

We start from your Form 1 schedule and any previous fire door register. If there is no register, our first visit builds one, numbering each door by location. Each later inspection uses the same numbers, so you can see at a glance which doors keep failing and why.

Standards and service frequency in SA

EquipmentHow oftenStandardSA source
Hinged fire doors Every 6 months AS 1851-2012 MBS 002 v3 (SA)
Other fire and smoke doors, shutters and passive fire elements The routine AS 1851-2012 sets for each element on your schedule AS 1851-2012 MBS 002 v3 (SA)
Annual Form 3 (ESP maintenance certificate) Within 60 business days after the end of each calendar year Planning, Development and Infrastructure (General) Regulations 2017 PlanSA Form 3

Who this is for

Certificates and reporting

Every visit ends with a written report listing each item tested, its location and result, and anything that needs attention. Building owners use it as the maintenance record behind their annual Form 3. We are qualified and authorised to carry out fire safety maintenance and sign off SA council ESP Form 2 and Form 3 maintenance documentation.

Ask us for a sample report if you want to see the format before you book.

Who does the work

  • FPAS Recognised BusinessFire Protection Accreditation Scheme
  • FPA Australia Bronze MemberFire Protection Association Australia
  • Engineers AustraliaMember of the national body for engineers
  • CBS PGE fire plumbing licenceConsumer and Business Services SA
  • Licensed for electrical test and tagAS/NZS 3760 testing

All licences and certificates are held by suitably qualified personnel, and we are fully insured.

Frequently asked questions

How often do fire doors need to be inspected in South Australia?
Hinged fire doors are inspected every 6 months. South Australia's maintenance instrument, MBS 002 (version 3), calls up AS 1851-2012 for fire doors. Other door types and passive fire elements have their own routines, and we schedule each one on your plan.
What gets checked in a fire door inspection?
The door leaf, frame, hinges, door closer, latch and seals, plus the door's tag or label and any signage. The most important test is simple: open the door fully, let go, and confirm it closes and latches by itself with nothing holding it back.
Can a fire door be propped open?
Not with a wedge, a chair or a hook. A fire door only works if it is closed when the fire starts. If a door must stay open for daily use, it can be fitted with a hold-open device that releases it when the fire alarm operates. Ask us about the doors you need held open.
What is passive fire protection?
It is the fire protection built into the building itself: fire-rated walls, floors and ceilings, fire doors, and the seals around pipes, cables and ducts where they pass through those walls. It needs no power or water. It works by keeping fire and smoke in one part of the building for long enough for people to get out.
What is fire stopping?
Fire stopping seals the gaps where services pass through a fire-rated wall or floor, such as cables, pipes and ducts. Each time a trade cuts a new hole and leaves it unsealed, the wall loses part of its fire rating. Penetrations should be sealed with a tested system that matches the wall's rating.
Do you repair fire doors and fire stopping?
Ask us. Every defect goes in your report with its location, and we'll tell you how it can be fixed and who can do the work.
Who is responsible for fire doors in a strata or leased building?
The building owner or strata corporation is responsible for maintaining the essential safety provisions, including fire doors on common property, and lodges the Form 3. Leases often pass day-to-day care to tenants, but a tenant who wedges a door open can still undo the owner's maintenance. Agree who checks what.

Related guides

Get a quote for fire doors and passive fire

We send quotes the same day and call back within 15 minutes during business hours. Prefer to talk? Call 08 8151 1040.

No obligation. We only use your details to reply to this request.

Book your next service

Tell us what's on site and we'll send a fixed price the same day.

Call 08 8151 1040 Get a quote