AS 1851-2012 is the Australian Standard for routine service of fire protection systems and equipment, setting what is checked and how often. In South Australia it applies through MBS 002, with frequencies from monthly to 5-yearly depending on the system.
It will appear on every fire service report you receive, so it helps to know how it works and what it means for your Form 3.
What AS 1851 is
AS 1851-2012, Routine service of fire protection systems and equipment, is published by Standards Australia. It is the national standard for servicing fire equipment once a building is occupied. For each type of system, it sets out:
- the tasks to carry out at each routine service
- how often each service is due, from monthly to 5-yearly and beyond
- what counts as a pass, and what must be reported as a defect
- what records must be kept
It covers the systems most buildings have, such as sprinklers, hydrants, hose reels, fire detection and alarm systems and portable extinguishers, along with passive elements such as fire doors.
Standards Australia’s catalogue lists AS 1851-2012 with one amendment, Amendment 1 of 2016, and shows the standard as pending revision. Until a new edition is published and South Australia’s MBS 002 calls it up, the 2012 edition is the one your reports should cite.
How AS 1851 applies in South Australia
AS 1851 is a standard, so it applies when a law or instrument calls it up. In South Australia that instrument is MBS 002 (version 3, May 2023), Maintaining the performance of essential safety provisions. MBS 002 replaced the older SA 76 and references AS 1851-2012 for fire protection equipment and AS/NZS 2293.2 for emergency lighting.
The chain looks like this:
- When a building is approved, the council or relevant authority issues a Form 1, the schedule of the building’s essential safety provisions (ESPs).
- When each ESP is installed, the installer signs a Form 2 certificate of compliance, which goes to whoever issues the certificate of occupancy.
- From then on, each ESP is maintained to MBS 002, which for fire equipment means the AS 1851-2012 tasks and frequencies.
- Each year, the owner lodges a Form 3 with council, within 60 business days after the end of the calendar year, certifying that the ESPs were maintained.
Service frequencies under MBS 002
| Equipment | How often |
|---|---|
| Portable fire extinguishers | Every 6 months, plus yearly and 5-yearly services |
| Fire hose reels | 6-monthly and yearly |
| Fire hydrants and boosters | Monthly to 5-yearly, by component and test |
| Fire detection and alarm systems | Monthly to 5-yearly |
| Hinged fire doors | Every 6 months |
| Emergency and exit lighting (AS/NZS 2293.2) | 6-monthly and yearly, plus monthly checks |
| Sprinklers, pumps and fire water tanks | On their AS 1851-2012 schedules for the system |
Your Form 1 is the starting point. It lists which ESPs your building has, so you know which rows apply to you.
Who can do the work
AS 1851 sets what is done, not who may do it. In South Australia, testing firefighting equipment connected to mains water needs CBS test and inspect registration (General, Hydrant and hose reel, or Trainee). Annual and longer tests, other than on hose reels, also need plumbing registration (CBS).
“AS 1851 certified” is not a thing
You will see fire businesses describe themselves as “AS 1851 certified”. There is no such certification. AS 1851 is a servicing standard. A business can work to it, but no body certifies businesses against it. If you are choosing a contractor, ask instead about their registrations, how they record results and how they report defects.
What a good AS 1851 report looks like
A report should let you, a council officer or an insurer see what was done without visiting the site:
- every item listed by location and identifier
- the service carried out (6-monthly, yearly, 5-yearly) and the date
- the result for each item, and each defect with its risk and recommended fix
- what was fixed on the day, and what is waiting for approval
AS 1851 and your Form 3
The Form 3 is the owner’s certificate. Your AS 1851 service reports are the evidence behind it. A maintenance contractor supplies the records and signs the contractor section for the work it did, but the Form 3 stays the owner’s obligation.
Class 1b buildings, and Class 3 to 9b buildings with a rise of 2 storeys or less and 500 m² or less, are exempt from lodging unless a section 157 notice or a performance solution applies. Class 1a and 10 buildings are outside the scheme. Exempt owners must still maintain their ESPs. Not maintaining ESPs or not lodging carries a $750 expiation and a maximum penalty of $10,000 (regulation 94 of the Planning, Development and Infrastructure (General) Regulations 2017).
See essential safety provisions and Form 3 and our annual fire safety checklist. To book servicing to AS 1851, such as fire extinguisher testing, call VD Fire & Electrical on 08 8151 1040.