Fire safety in aged care is about time
Residents in aged care often cannot leave a building on their own. That is why the National Construction Code puts most aged care homes in Class 9c and asks more of them than almost any other building: sprinklers throughout, and smoke detection connected to monitoring so help is called the moment a detector operates.
Those systems only buy staff time if they work. Our job is to keep them working, keep the records that prove it, and help your team practise what to do when the alarm sounds.
What we look after in a Class 9c home
A typical Adelaide aged care home has most of the following on its Form 1 schedule of essential safety provisions (ESPs). We service each one on the schedule South Australia’s maintenance standard, MBS 002, sets.
| System | What it does | How often it is serviced |
|---|---|---|
| Sprinklers | Control a fire in the room where it starts | On the AS 1851-2012 schedule for your system |
| Smoke detection and alarm | Detects smoke, sounds the alarm and calls monitoring | Monthly to 5-yearly |
| Exit and emergency lighting | Lights the way out if power fails | 6-monthly and yearly, plus monthly checks |
| Fire doors | Hold fire and smoke in one compartment | Hinged fire doors every 6 months |
| Hose reels and hydrants | Water for staff and the fire brigade | Hose reels 6-monthly and yearly. Hydrants monthly to 5-yearly |
| Extinguishers and blankets | First attack on a small fire | Every 6 months, plus yearly and 5-yearly |
Testing firefighting equipment connected to mains water needs CBS test and inspect registration, and annual and longer tests (other than on hose reels) need plumbing registration. We hold a CBS PGE fire plumbing licence and are FPAS accredited (Fire Protection Accreditation Scheme). Ask us which registrations apply to the tests on your systems.
Fire risk assessments
We carry out fire risk assessments for aged care homes. We walk the building, check what is installed against its Form 1 schedule, look at exits, compartments and the paths staff would use to move residents, and give you a written report of what is in place, what is overdue and what needs fixing. See our fire safety inspections and audits page. The first fire safety audit is free.
Installation and maintenance
We install and maintain the fire safety systems an aged care home relies on, including smoke detectors, fire alarms, extinguishers, hydrants and emergency lighting, as well as servicing the sprinklers, hose reels and fire doors in the table above. Electrical installation work is done by our licensed electrical contractor. New work and upgrades are quoted per site.
Fire doors and compartments
Aged care buildings are divided into fire and smoke compartments, so staff can move residents away from a fire into the next compartment rather than out of the building. That plan only works if the doors between compartments close and seal.
In a busy care home, those doors are under constant pressure. They get wedged open for trolleys, held back with a chair on a hot day, or damaged by beds and lifters. Closers wear out and smoke seals tear. We inspect hinged fire doors every 6 months, as MBS 002 requires, and report each door by its location so maintenance staff can find it.
If doors need to stay open for daily care, ask us about hold-open devices that release on alarm.
What the owner lodges on the Form 3, and what we supply
Every year, the building owner certifies to council that the ESPs have been maintained. This is the Form 3, and it must be lodged within 60 business days after the end of each calendar year. MBS 002 exempts only Class 1b buildings and small Class 3 to 9b buildings, so a Class 9c home is not exempt.
The Form 3 stays the owner’s obligation. What we do is make it straightforward:
- a maintenance record for every ESP on your Form 1, for every service in the year
- defects listed with what was fixed and when, so nothing open is carried into the certificate
- the contractor section of the Form 3 signed for the work we did
- a year-end summary ready for your facility manager to check and sign
- ESP logbook entries for every visit
Councils cite $750 expiations for not lodging a Form 3 or not maintaining ESPs, and penalties of up to $10,000 if prosecuted. See essential safety provisions and Form 3.
Fewer false call-outs from monitored alarms
Because a Class 9c alarm system is connected to monitoring, an unwanted alarm can bring a fire brigade response. It also wakes and distresses residents, interrupts care, and has to be investigated. Most unwanted alarms come from something that can be fixed.
Our monitored alarm care covers:
- Event review. After an unwanted alarm we look at which detector operated, when, and what was happening nearby.
- Detector type and location. A smoke detector beside a kitchenette or an ensuite door may suit a different detector type. We flag it and quote the change for your approval.
- Contractor isolation procedure. Hot work, sanding and dusty works set off detectors. We help you set a written procedure for isolating only the zones affected, for only as long as needed, and restoring them afterwards.
- Routine testing on schedule. Detectors and alarm equipment are tested on the MBS 002 schedule, so faults are found in a test, not in the middle of the night.
Tell us who provides your monitoring connection and we’ll coordinate testing with them.
Supporting outcome 2.10 drills
The strengthened Aged Care Quality Standards (outcome 2.10) require emergency plans that are regularly tested. Under the WHS Regulations, every workplace also needs an emergency plan. For an aged care home, a fire drill is the most practical test you can run.
We can help you prepare for drills and show the evidence afterwards:
- evacuation diagrams that match the building as it is today
- a check that exit routes, exit signs and fire doors work before the drill
- updates to the emergency plan when the building or the resident mix changes
Keep a written record of each drill: the date, the scenario, who took part and what to improve. Ask us about being on site for a drill. We also draft and design emergency and evacuation plans. See emergency management plans.
Staff fire training
Every aged care worker should know how to raise the alarm, use an extinguisher or blanket, and move residents towards safety. Staff practise best on the routes and equipment they would use, in your own building. We write the emergency plan and evacuation diagrams that training is built on, and keep the extinguishers, blankets and alarms in working order.
Test and tag for aged care
Aged care homes have hundreds of portable appliances, from bed motors and hoists to kettles and residents’ own electrical items. We can test and tag them on the same visit as your fire servicing. See test and tag.
Records an assessor can follow
Aged care providers answer to more than one regulator. Council wants the Form 3. The Aged Care Quality and Safety Commission wants evidence that emergency plans are tested. Your own board wants to know nothing is overdue. Our reports are set out so one set of records serves all three:
- every service visit, by system and by date
- each defect, its risk, the quote and the date it was fixed
- drill records and emergency plan updates kept with the system records
- a year-end summary that matches your Form 1 schedule line by line
How we work with aged care sites
Aged care is a home first. We book visits to fit around care routines, tell staff before any alarm or bell is tested, and keep noisy tests short. Each visit ends with a written report your facility manager can file straight into the compliance system.
The rules that apply
| Requirement | What it means | Standard | SA source |
|---|---|---|---|
| Class 9c aged care buildings | Sprinklers throughout, plus smoke detection connected to monitoring | NCC 2022 Volume One, Part E1 | ABCB NCC 2022 |
| Emergency and disaster plans | Regularly tested and reviewed | Strengthened Aged Care Quality Standards, outcome 2.10 | Aged Care Quality and Safety Commission |
| Annual Form 3 (ESP maintenance certificate) | Within 60 business days after the end of each calendar year | Planning, Development and Infrastructure (General) Regulations 2017 | PlanSA Form 3 |
| Fire detection and alarm systems | Monthly to 5-yearly | AS 1851-2012 | MBS 002 v3 (SA) |
| Emergency and exit lighting | 6-monthly and yearly, plus monthly checks | AS/NZS 2293.2 | MBS 002 v3 (SA) |
| Hinged fire doors | Every 6 months | AS 1851-2012 | MBS 002 v3 (SA) |
| Portable extinguishers and fire blankets | Every 6 months (extinguishers also yearly and 5-yearly) | AS 1851-2012 | MBS 002 v3 (SA) |
| Workplace emergency plan | Prepared, maintained and implemented | WHS Regulations (SA), regulation 43 | SafeWork SA |