Based in Enfield. Working across Adelaide and regional SA. 08 8151 1040

Fire hose reel maintenance for Adelaide property owners

Fire hose reels in South Australian buildings must be serviced every 6 months and every year, under MBS 002 and AS 1851-2012. Because they're connected to mains water, the testing must be done by someone with a CBS test and inspect registration.

Fire hose reel mounted on a warehouse wall beside an emergency exit door
A hose reel near an exit, where it can be reached quickly. From one of our jobs.

Fire hose reels in South Australian buildings are serviced every 6 months and every year under MBS 002 and AS 1851-2012. Because they’re connected to mains water, the tester needs a CBS test and inspect registration.

A reel can look perfectly good in its cabinet and still have a perished hose, a seized valve or a blocked nozzle, which is why testing is built into routine servicing.

VD Fire & Electrical tests and services hose reels in commercial, industrial and multi-residential buildings across Adelaide, and the same questions come up again and again: how often it needs doing, what’s checked and what you should keep on file.

Fire hose reel maintenance in Adelaide

A fire hose reel is a length of hose wound on a drum and permanently connected to your building’s water supply. It’s designed so that occupants or trained staff can tackle a small fire early with a continuous supply of water, which a portable extinguisher can’t offer once it runs out.

That only works if the reel does what it’s supposed to when someone grabs it. Hoses perish with age, seals dry out and valves seize when they’re never operated. None of this is obvious from a glance at the cabinet, which is why hose reel maintenance relies on a scheduled, hands-on service rather than a visual check by whoever happens to be passing.

How often fire hose reels are tested

South Australia’s maintenance standard is MBS 002 (version 3, May 2023). It replaced SA 76 and calls up AS 1851-2012, the Australian Standard for routine service of fire protection systems and equipment. For fire hose reels it sets two service levels:

  • Every 6 months: a routine service of each reel.
  • Every year: a more thorough service.

Your building’s Form 1, the schedule of essential safety provisions issued by council or the relevant authority, lists whether hose reels are one of your building’s ESPs and the maintenance they need. If you’re not sure what your current schedule is, your last service report or the reel’s tag is the best place to start.

Who can test fire hose reels in SA

Hose reels are connected to mains water, so testing them is licensed work. According to Consumer and Business Services, the tester needs a CBS test and inspect registration: General, Hydrant and hose reel, or Trainee (working under direct supervision). Hose reels are the exception to the rule that annual and longer AS 1851 tests also need a plumbing registration, so a test and inspect registration covers all hose reel testing.

VD Fire & Electrical is FPAS accredited (Fire Protection Accreditation Scheme) and holds a CBS PGE fire plumbing licence. Ask us which registrations apply to the tests on your site.

What fire hose reel inspection in Adelaide involves

A proper hose reel service is hands-on. For a typical reel, a technician will:

  • Confirm the reel is accessible, with the cabinet or recess clear, clearly marked and in good repair.
  • Check the mounting, hose guide and swing arm (where fitted) for damage, corrosion or looseness.
  • Run the hose out to confirm it unwinds freely and rewinds properly.
  • Pressurise the reel and check for leaks at the stop valve, nozzle, hose and fittings.
  • Run water through the nozzle to confirm flow.
  • Check the service tag is attached, and update it.
  • Record the results, including any defects and recommended repairs.

Defects are written up against the reel’s location, so you can see exactly what needs attention and prioritise repairs. A reel that fails should be repaired or replaced promptly rather than left in place, because an out-of-service reel is a compliance gap as well as a safety one. If you’d like your reels inspected and written up, you can request a quote.

Compliance requirements and standards for fire hose reels

Three things sit behind most of what a property owner needs to know. AS 1851-2012, through MBS 002, covers routine servicing. AS 2441 covers how fire hose reels are installed, as the National Construction Code requires. And your building’s approval documents and Form 1 set out whether hose reels are required in the first place.

Records matter as much as the service itself. You should be able to produce a current service report, and each reel should carry a tag showing when it was last serviced. Where hose reels are listed as essential safety provisions, those records are the evidence behind the owner’s annual Form 3, which is lodged with council within 60 business days after the end of each calendar year. Smaller buildings exempt from lodging a Form 3 must still maintain their ESPs.

If servicing falls behind, the consequences are practical. Not lodging a Form 3 or not maintaining ESPs carries a $750 expiation and a maximum penalty of $10,000 under regulation 94 of the Planning, Development and Infrastructure (General) Regulations 2017. A lapsed schedule is far easier to fix before someone asks about it than after.

Signs your fire hose reel needs attention sooner

Between scheduled services, it’s worth a quick look for these warning signs:

  • The hose is stiff, cracked, bulging or visibly perished.
  • The reel doesn’t unwind smoothly, or the hose catches.
  • Water weeps from the nozzle, valve or fittings.
  • The cabinet is blocked, damaged or missing its signage.
  • The service tag is missing or out of date.

Any of these is a reason to arrange a service early rather than wait for the next scheduled visit.

A fire hose reel earns its keep on the one day it’s needed. Until then, keep access clear, keep the service tags current and keep the reports on file. If you’re not sure where your reels stand, call VD Fire & Electrical on 08 8151 1040 and we’ll help you work it out. See also our fire hose reel testing service, and our guides to fire hydrant inspections and AS 1851.

Frequently asked questions

How often do fire hose reels need to be tested in SA?
Every 6 months and every year. MBS 002, South Australia's maintenance standard, calls up AS 1851-2012, which sets a 6-monthly service and a more thorough yearly service for fire hose reels.
Who can test fire hose reels in South Australia?
Someone with a Consumer and Business Services test and inspect registration (General, or Hydrant and hose reel, or a Trainee under direct supervision). Unlike hydrants and sprinklers, the annual hose reel test doesn't need a separate plumbing registration.
Which standard covers hose reel installation?
AS 2441 covers the installation of fire hose reels. AS 1851-2012 covers their routine servicing once installed.
Are fire hose reels part of my Form 3?
If your building's Form 1 lists hose reels as an essential safety provision, yes. The service records are the evidence behind the owner's annual Form 3 to council.

Book your next service

Tell us what's on site and we'll send a fixed price the same day.