AS/NZS 3760:2022 is the standard for in-service inspection and testing of plug-in electrical equipment and RCDs, the standard behind test and tag. In South Australia it is guidance rather than law: the legal duty sits in the WHS Regulations, and SafeWork SA uses the standard for how often and how to test.
What AS/NZS 3760 is
AS/NZS 3760:2022, In-service safety inspection and testing of electrical equipment and RCDs, is a joint Australian and New Zealand Standard. It covers electrical equipment once it is in service: the leads, tools, power boards and appliances that plug into a socket, and residual current devices (RCDs or safety switches).
Standards Australia’s overview of the standard lists what it covers:
- Inspection procedures, the visual check that catches most faults
- Testing procedures, such as earth continuity, insulation resistance and polarity
- Inspection and testing frequency
- Documentation and tagging
- Competency requirements for the person doing the work
Standards Australia’s catalogue lists AS/NZS 3760:2022 as current, with one amendment (Amendment 1, published December 2022). It replaced the 2010 edition.
Guidance, not law, in South Australia
AS/NZS 3760 is not itself law in South Australia. The legal duty sits in the Work Health and Safety Regulations 2012 (SA). Regulations 150 and 163 to 165 deal with electrical equipment and RCDs, including regular inspection and testing by a competent person of equipment used in hostile operating environments. SafeWork SA’s guidance on inspection and testing of electrical equipment treats AS/NZS 3760:2022 as the guidance for how to do it.
In practice, following AS/NZS 3760 is the accepted way to show you have met your duty. If an inspector asks how you manage electrical equipment, a test and tag register kept to the standard is the evidence.
SafeWork SA test intervals
SafeWork SA sets intervals by type of workplace:
| Workplace | Interval |
|---|---|
| Construction (portable equipment) | Every 3 months |
| Hire equipment | Inspected before each hire, tested every 3 months |
| Manufacturing and commercial cleaning | Every 6 months |
| Other hostile environments | At least every 12 months |
| Low-risk areas such as offices | Up to 5 years |
A hostile environment is one where equipment is exposed to things that can damage it, such as moisture, heat, vibration, mechanical damage, corrosive chemicals or dust. The 5-year interval applies only where equipment isn’t flexed in normal use, isn’t open to abuse and isn’t in a hostile environment. See our guide to how often test and tag is needed.
What happens in a test
A typical test under AS/NZS 3760 has two parts.
- Visual inspection. The tester checks the plug, lead, cord grips and casing for damage, burns, exposed wires, missing parts and unsafe repairs. Many faults are found here.
- Electrical tests. Depending on the equipment, the tester checks earth continuity, insulation resistance and polarity with a portable appliance tester.
WHS regulation 150 says the record of each test must show who did it, the date, the result and when the next test is due, and the record can be a tag. Equipment that fails is taken out of service, labelled so nobody uses it, and listed in the report so it can be repaired or thrown out.
RCDs and safety switches
AS/NZS 3760 also covers RCDs, both portable units and those fixed in the switchboard. An RCD cuts power when current leaks to earth, which is what protects a person from a fatal shock. Testing checks that it trips, and how quickly. See RCD testing and our guide to how often RCDs should be tested.
Tag colours
Colour-coded tags are not a legal requirement in SA. The quarterly colour rotation is the recommended tag coding in SafeWork SA’s guideline for construction and demolition sites, where AS/NZS 3012 applies under WHS regulation 163. See our guide to test and tag colours.
Records you should keep
A test and tag register should show each item, where it is, the test date, the result, the next test date and who tested it. It should also record failed items and what happened to them. Keep it with your WHS records.
3-phase equipment
Three-phase leads and equipment are tested under the same framework as single-phase items, with test equipment suited to them. See 3-phase appliance testing.
To book test and tag to AS/NZS 3760:2022, from $3.50 + GST per item, call VD Fire & Electrical on 08 8151 1040 or see test and tag.