Fire door ratings and inspections in South Australia

A fire door's rating is its fire-resistance level (FRL), three numbers such as -/60/30 that give the minutes of structural adequacy, integrity and insulation, with a dash where there is no requirement. In South Australia, hinged fire doors are inspected every 6 months under MBS 002, and inspections are quoted per site on the number of doors.

A fire door’s rating tells you how long it is built to hold back fire, in minutes, across three tests. In South Australia, hinged fire doors in buildings with essential safety provisions are inspected every 6 months, and the tags on the door and frame show what rating it was made to.

What does a fire door rating mean?

The rating is the door’s fire-resistance level, or FRL. The Australian Building Codes Board explains it in its NCC Tutor lesson on fire safety as a graded performance over time of a building element exposed to a test fire, measured in minutes. AS 1530.4 is the standard generally used to test it.

An FRL always has three parts, in this order:

Part What it measures
Structural adequacy How long the element stays stable and carries its load
Integrity How long it resists the passage of flames and hot gases
Insulation How long the side away from the fire stays below a set temperature

If one part does not apply, the FRL shows a dash for it. So a fire door marked -/60/30 has:

  • no structural adequacy rating, because a door doesn’t hold up the building
  • 60 minutes of integrity, so flames and hot gas are held back for an hour
  • 30 minutes of insulation, so the far side stays cool enough for 30 minutes

The ABCB’s own worked example shows why doors often carry ratings like this. For the openings in a fire wall it uses, a self-closing or automatic closing door had no structural adequacy requirement, had to resist flames and hot gases for at least 60 minutes, and had to limit the temperature on the far side for at least 30 minutes.

The door is only part of it. The wall it sits in has its own FRL, and the door is chosen to suit it.

What is on a fire door tag?

Queensland’s fire service publishes a clear fire doors information sheet. It says a fire door is a set made up of the door leaf, the frame and its hardware, such as closers, handles, locks, vision panels and air grilles, with matching tags on the door and frame. Fire doors must be self-closing and latching.

Tags follow AS/NZS 1905.1. The sheet lists what the tag must show:

  • the component standard, AS/NZS 1905.1
  • the fire-resistance level, for example -/60/30
  • the manufacturer’s name
  • the applicant’s name
  • the certifier
  • the door tag number
  • the year of manufacture

Never paint over, remove or cover a fire door tag. It is how anyone inspecting the door can tell what it was made and certified to.

How often are fire doors inspected in SA?

In South Australia, the maintenance of essential safety provisions follows Ministerial Building Standard MBS 002, as the MFS confirms. MBS 002 version 3 calls up AS 1851-2012, and hinged fire doors are inspected every 6 months. Other door types and passive fire elements follow the routines AS 1851 sets for them.

The owner then lodges a Form 3 with council, within 60 business days after the end of each calendar year, to confirm the building’s essential safety provisions were maintained. Your fire door reports are part of the records behind it. See essential safety provisions and Form 3.

What does a fire door inspection check?

On each door, the inspector checks:

  • the door leaf and frame for damage, holes and gaps
  • the hinges, closer and latch
  • the smoke and fire seals
  • any hold-open device, and that it releases when it should
  • the tags on the leaf and frame
  • the signs on and beside the door
  • any added hardware, such as locks, kick plates or bolts

Then comes the simplest test of all. Open the door fully, let it go, and confirm it closes and latches by itself with nothing in the way. Each defect is recorded by door location, so it can be fixed and closed out before your Form 3.

What are the most common fire door failures?

Most fire door defects come from everyday use rather than age.

  • Wedged or propped open. A fire door does nothing if it is open when the fire starts. Queensland’s fire service says the movement of a fire door must never be blocked by a wedge, chock or other obstacle, and calls wedging illegal there. If a door needs to stay open, fit a hold-open device that releases it when a smoke detector, the fire alarm or the sprinklers operate.
  • Damaged or missing seals. Smoke and fire seals get torn off when a door sticks, or worn away by trolleys.
  • A closer that no longer latches. Closers are often turned down because a door feels heavy, until it stops latching.
  • Non-compliant hardware. New locks, security doors, peepholes or kick plates fitted without checking the rating. Queensland’s fire service says all fittings must comply with the door set’s fire rating.
  • Holes and cut-outs. Old hardware removed and the holes left open.
  • Something in the way. A bin, chair or stack of boxes in the door’s swing.

The Queensland sheet also warns that some fire doors in buildings constructed before 1990 contain asbestos insulation. Don’t drill, cut or sand an older fire door until you know what is inside it.

Fire doors and the rest of your passive fire protection

Fire doors are one part of a building’s passive fire protection. The walls, floors and ceilings around them, and the seals where cables and pipes pass through, have to hold their rating too. A new cable run through a fire wall can undo a perfectly maintained door beside it. See fire doors and passive fire.

VD Fire & Electrical inspects fire doors in offices, apartments and care buildings across Adelaide, from the CBD to Unley. Inspections are quoted per site on the number of doors, and your first fire safety audit is free. Call 08 8151 1040.

Frequently asked questions

What does FRL stand for?
Fire-resistance level. The ABCB describes it as a measure of how long a building element can control the spread of fire, gases and heat and keep its structural strength when exposed to fire. It is measured in minutes, in a standard fire test, generally to AS 1530.4.
Can I fit a new lock, security door or peephole to a fire door?
Not with ordinary hardware. Queensland's fire service says the hardware on a fire door is part of the rating the door is certified to, and that all fittings must comply with the fire rating of that door set. Check with the door's manufacturer or a fire door specialist before you change anything.
Can a fire door be held open?
Not with a wedge or chock. A fire door can be held open by a device that releases it when a smoke detector, the fire alarm or the sprinklers operate, so it closes by itself in a fire. Queensland's fire service says wedging a fire door is illegal there and attracts a penalty.
Who is responsible for fire doors in South Australia?
The building owner. Fire doors are usually listed on the building's schedule of essential safety provisions, and the MFS says owners must lodge a Form 3 with council each year to confirm those provisions were maintained. A tenant who wedges a door open can still undo that work, so agree who checks what.
How much does a fire door inspection cost?